Issue title: Digital transformation through advances in artificial intelligence and machine learning
Guest editors: Hasmat Malik, Gopal Chaudhary and Smriti Srivastava
Article type: Research Article
Authors: Malik, Hasmata | Ahmad, Md Waseemb | Alotaibi, Majed A.c; * | Almutairi, Abdulazizd
Affiliations: [a] BEARS, University Town, NUS Campus, Singapore | [b] Department of Electrical and Electronics Engineering Department, NIT Surathkal, India | [c] Department of Electrical Engineering, College of Engineering, King Saud University, Riyadh, Saudi Arabia | [d] Department of Electrical Engineering, College of Engineering, Majmaah University, Al Majma’ah, Saudi Arabia
Correspondence: [*] Corresponding author. Majed A. Alotaibi, Department of Electrical Engineering, College of Engineering, King Saud University, Riyadh 11421, Saudi Arabia. E-mail: [email protected].
Abstract: PMU can directly measure positive sequence voltage, phase and system frequency. In this paper, the design and implementation for optimum placement of PMU in power system network (PSN) has been performed using 5 different intelligent approaches at an emulation platform. Different case studies based on IEEE 7, 14 and 30 bus system have been performed and analyzed. In the studies, PMU device is used for the measurement of voltage and current magnitude as well as its phase and its performance has been compared with measured real signals of PSN. PMU measurement gives the accurate results and reliability to PSN. But PMUs are not economical, so PSN operator needs to install a minimum number of PMU in PSN so that system should be fully observable in a real-time scenario. In this paper for optimal placement of PMU, five different intelligent methods have been analyzed for three different bus systems and obtained results are compared. For the further validation of selected PMUs for the PSN, a state estimation using WLS algorithm has been performed using conventional data and PMU data on IEEE14 and IEEE30 bus systems. The obtained results for voltage estimation error and phase estimation error with and without PMU data are compared.
Keywords: Condition monitoring, PMU, placement, wide area monitoring, smart grid
DOI: 10.3233/JIFS-189752
Journal: Journal of Intelligent & Fuzzy Systems, vol. 42, no. 2, pp. 827-839, 2022
IOS Press, Inc.
6751 Tepper Drive
Clifton, VA 20124
USA
Tel: +1 703 830 6300
Fax: +1 703 830 2300
[email protected]
For editorial issues, like the status of your submitted paper or proposals, write to [email protected]
IOS Press
Nieuwe Hemweg 6B
1013 BG Amsterdam
The Netherlands
Tel: +31 20 688 3355
Fax: +31 20 687 0091
[email protected]
For editorial issues, permissions, book requests, submissions and proceedings, contact the Amsterdam office [email protected]
Inspirees International (China Office)
Ciyunsi Beili 207(CapitaLand), Bld 1, 7-901
100025, Beijing
China
Free service line: 400 661 8717
Fax: +86 10 8446 7947
[email protected]
For editorial issues, like the status of your submitted paper or proposals, write to [email protected]
如果您在出版方面需要帮助或有任何建, 件至: [email protected]